Batteries & backup · Australia

Battery runtime calculator

Estimate usable storage and backup runtime for blackouts or self-consumption. Enter kWh (or Ah + V), usable fraction, efficiency and load watts.

Results

Nominal capacity
—
Usable energy
—
Estimated runtime
—
Runtime (hours)
—

Methodology

Usable Wh = nominal Wh × depth of discharge × inverter efficiency. Runtime hours = usable Wh ÷ connected load watts.

Worked example

10 kWh battery, 90% usable, 94% inverter path, 1 000 W critical load → usable ≈ 8.46 kWh → runtime ≈ 8.5 hours.

Assumptions and limitations

Ignores temperature derating, age and surge starting watts.

Use continuous watts for runtime. Motor starting needs the inverter sizing calculator.

FAQ

Continuous vs surge?

This tool uses continuous watts for runtime.

Why enter usable fraction?

Manufacturers reserve capacity. Enter DoD so runtime is not overstated.

Related calculators

All Australia calculators · Guides for Australia

Sources and review

Usable Wh = nominal Wh × DoD × inverter efficiency; runtime = usable Wh ÷ load W.

Last reviewed: 23 November 2026