Batteries & backup · South Africa
Battery runtime calculator
Plan critical-load backup for load-shedding. Enter battery kWh (or Ah + voltage), usable depth of discharge, inverter efficiency and continuous load.
Results
Methodology
Usable Wh = nominal Wh × depth of discharge × inverter efficiency. Runtime hours = usable Wh ÷ connected load watts. Ah capacity converts as (Ah × V) ÷ 1000 = kWh.
Worked example
A 5 kWh battery, 90% usable DoD, 92% inverter efficiency and a 500 W load → usable ≈ 5 × 0.9 × 0.92 = 4.14 kWh → runtime ≈ 4 140 Wh ÷ 500 W ≈ 8.3 hours.
Assumptions and limitations
Ignores temperature, battery age, Peukert effects on lead-acid, inverter idle draw and surge loads. Not a substitute for an installer’s design.
Most load-shedding systems back up selected circuits (lights, Wi‑Fi, fridge) rather than the whole house. Size for the continuous watts you will actually run.
FAQ
Can I run the whole house?
Usually no during long outages. Many systems back up lights, Wi‑Fi, fridge and selected plugs only.
Ah or kWh?
Lithium packs are often rated in kWh. For Ah ratings, multiply by nominal voltage and divide by 1 000.
Is this exact?
No. It is an estimate of usable energy under stated assumptions — real runtime varies.
Related calculators
- Inverter size calculator — Estimate continuous and surge inverter capacity from appliance loads and safety headroom.
- Electricity cost calculator — Convert watts and hours into daily, monthly and annual rand costs.
- Solar panel requirement calculator — Estimate array size and panel count from daily kWh and peak sun hours.
Sources and review
Usable Wh = nominal Wh × DoD × inverter efficiency. Runtime = usable Wh ÷ load W.
Last reviewed: 23 November 2026