Batteries & backup · United States

Battery runtime calculator

Size expectations for a critical-load panel or whole-home backup discussion. Enter kWh (or Ah + V), usable fraction, inverter efficiency and continuous watts.

Results

Nominal capacity
—
Usable energy
—
Estimated runtime
—
Runtime (hours)
—

Methodology

Usable Wh = nominal Wh × depth of discharge × inverter efficiency. Runtime hours = usable Wh ÷ connected load watts. Ah capacity converts as (Ah × V) ÷ 1000 = kWh.

Worked example

13.5 kWh battery, 90% usable, 94% round-trip inverter path, 1 200 W critical load → usable ≈ 11.42 kWh → runtime ≈ 9.5 hours.

Assumptions and limitations

Does not model BMS reserves, temperature derating, generator auto-start or surge locked-rotor amps. Not a UL design document.

Use continuous watts for runtime. Motor starting needs a separate surge check (inverter sizing in Phase 2). Enter usable fraction so runtime is not overstated.

FAQ

Continuous vs surge?

This tool uses continuous watts for runtime. Motor starting needs a separate surge check.

Usable vs nameplate kWh?

Manufacturers reserve capacity. Enter usable fraction (DoD) so runtime is not overstated.

Whole-home backup?

Whole-home loads can exceed storage quickly. Many installs use a critical-load panel instead.

Related calculators

All United States calculators · Guides for United States

Sources and review

Usable Wh = nominal Wh × DoD × inverter efficiency; runtime = usable Wh ÷ load W.

Last reviewed: 23 November 2026